S.L. 465.3 · Control Of Legionella Regulations (S.L. 465.3)

S.L. 465.3 ст. 10Action levels following microbiological monitoring of cooling tower systems and evaporative condensers.

ДействуетОфициальный текст

(1) The responsible person must ensure that the actions following microbiological monitoring of cooling towers and evaporative condensers is in accordance with the procedures laid down in Schedule 2.

(2) The responsible person shall immediately inform the Superintended of any situation provided for in Schedule 2.

(3) The responsible person shall carry out any further monitoring and remedial actions as may be directed by the Superintendent.

(4) The Superintendent may require the systems or part thereof to be shutdown until all necessary remedial actions have been taken by the responsible person and until microbiological sampling results of any system would have returned within the recommended acceptable levels as indicated in Schedule 2.